S&A CWFL (T-800/DVT) chiller error codes: what each code means

Updated:

Short answer

The S&A CWFL (T-800/DVT) chiller has 22 codes. The table explains each one and lists the usual causes. Start with the cause that is easiest to rule out.

Models: CWFL-1000 / CWFL-1500 / CWFL-2000 / CWFL-3000 / CWFL-4000 / CWFL-6000 / CWFL-8000 / CWFL-12000 / CWFL-15000 / CWFL-20000 / CWFL-30000 / CWFL-40000 / CWFL-60000 / RMFL-1000 / RMFL-2000 / RMFL-3000 / RMFL-6000 / CWFL-2000NP / CWFL-3000NP

Codes, meaning and causes

Code What it means Possible causes How to fix
E00 Communication fault alarm Communication cable break between the control panel and the controller
E01 Laser source line coolant flow level alarm Blockage or pressure drop in the laser source line
E02 Cutting head line coolant flow level alarm Blockage or pressure drop in the cutting head line
E03 Ambient temperature critically high alarm High air temperature around the chiller
E04 Laser source line temperature critically low alarm Overcooling of water in the source circuit
E05 Laser source line temperature critically high alarm Overheating of water in the source circuit
E06 Cutting head line temperature critically low alarm Overcooling of water in the cutting head circuit
E07 Cutting head line temperature critically high alarm Overheating of water in the cutting head circuit
E08 Incorrect phase sequence or phase loss Wrong phase sequence or missing phase in the 380 V supply
E09 Compressor overload Compressor overcurrent protection triggered
E10 Laser source line pump overload Source pump motor overload
E11 Pump overload on the cutting head line Overload of the cutting head pump motor
E12 High pressure alarm in the refrigeration system Refrigerant pressure above the limit
E13 Refrigeration system low-pressure alarm Refrigerant pressure drop (leak)
E14 Ambient temperature sensor fault Ambient temperature sensor wire break or short circuit
E15 Source line temperature sensor fault Source line temperature sensor wire break or short circuit
E16 Head line temperature sensor fault Wire break or short circuit in the cutting head line sensor
E17 Coolant conductivity too high High water electrical conductivity (ion contamination)
E18 Coolant conductivity too low Conductivity sensor malfunction
E19 Coolant level critically low Critically low water level in the tank
E20 Post-radiator air temperature sensor fault Wire break or short circuit in the radiator air temperature sensor
E21 Post-radiator air temperature too high Overheating of air downstream of the radiator

Every code by brand, with causes and fixes, is in the SBM Laser Help reference guide: servo drives, chillers and machine alarms.Reference guide in the app →

Related questions

What does error E00 mean on S&A CWFL (T-800/DVT)?
Communication fault alarm. Common causes: Communication cable break between the control panel and the controller.
How do I fix a S&A CWFL (T-800/DVT) chiller error?
Check the causes listed in the table first. Step-by-step fixes for every code are in the SBM Laser Help app: Google Play, App Store, web and Telegram.
Which models use these codes?
CWFL-1000 / CWFL-1500 / CWFL-2000 / CWFL-3000 / CWFL-4000 / CWFL-6000 / CWFL-8000 / CWFL-12000 / CWFL-15000 / CWFL-20000 / CWFL-30000 / CWFL-40000 / CWFL-60000 / RMFL-1000 / RMFL-2000 / RMFL-3000 / RMFL-6000 / CWFL-2000NP / CWFL-3000NP

Codes and causes are compiled from the manufacturers' manuals. A code can mean something else in another firmware version: always check the manual for your equipment.

Need the numbers for your exact machine?

See what is inside

SBM Laser Help carries cutting and piercing parameter tables by material, thickness and gas, photo diagnosis of cut defects, machine and chiller error codes, and gas consumption calculators. Free account, no card.